Distribution Box Knowledge for Low-Voltage Electrical Works

2022-09-24넶Views: 288

I. Working Principle of a Distribution Box

A distribution box assembles switchgear, measuring instruments, protective devices and auxiliary equipment in an enclosed or semi-enclosed metal cabinet or panel according to electrical wiring requirements, forming a low-voltage distribution device. During normal operation, circuits can be connected or disconnected by manual or automatic switches. In the event of a fault or abnormal operation, protective devices cut off the circuit or give an alarm. Measuring instruments can display various operating parameters, and some electrical parameters can be adjusted, with prompts or signals given for deviations from normal operating conditions. Distribution boxes are commonly used in power generation, distribution and substation facilities.

II. Structure and Applications of Distribution Boxes

(I) Structure

Distribution boxes, together with distribution cabinets, distribution boards and distribution panels, are complete assemblies for the centralized installation of switches, instruments and other equipment, and provide wiring guidance for integrated distribution boxes.

 

 

(II) Applications

Applications of distribution boxes: to distribute electrical energy reasonably and facilitate switching operations of circuits. They have a relatively high safety protection rating and can visually indicate the conduction status of circuits. They are easy to manage and facilitate maintenance when circuit faults occur. Elevator distribution box AC contactor replacement.

(III) Categories

Common distribution boxes are made of wood or metal. Because metal distribution boxes offer a higher protection rating, metal ones are more widely used.

Classified by structural features and applications:

(1) Fixed-panel switchgear, often called a switchboard or distribution panel. It is an open-type switchgear with a panel shield; the front provides protection, while live parts at the back and sides are still accessible. Its protection rating is low, so it can only be used in industrial and mining enterprises with low requirements for power supply continuity and reliability, for centralized power supply in substation rooms.

(2) Protected (i.e., enclosed) switchgear refers to low-voltage switchgear in which all sides except the mounting surface are enclosed. The switching, protection, monitoring and control electrical components of such cabinets are all installed in an enclosed housing made of steel or insulating material, and the cabinet can be installed against or away from a wall. Isolation between circuits inside the cabinet may be omitted, or grounded metal plates or insulating plates may be used for isolation. Usually the door and the main switch operation are mechanically interlocked. There is also protected desk-type switchgear (i.e., a console), with control, measurement, signal and other electrical devices mounted on the panel. Protected switchgear is mainly used as distribution equipment at process sites.

(3) Drawer-type switchgear. This type of switchgear uses an enclosed housing made of steel plate, and the electrical components of incoming and outgoing circuits are all installed in withdrawable drawers, forming functional units that can perform a certain type of power supply task. Functional units are separated from busbars or cables by grounded metal plates or functional plates made of plastic, forming three zones: busbar, functional unit and cable. There are also isolation measures between functional units. Drawer-type switchgear has high reliability, safety and interchangeability and is relatively advanced; most switchgear produced today is of the drawer type. They are suitable for industrial and mining enterprises and high-rise buildings with high requirements for power supply reliability, as centrally controlled distribution centers.

(4) Power and lighting distribution control boxes. They are mostly enclosed and vertically mounted. Their enclosure protection ratings vary with the application. They are mainly used as distribution equipment at production sites of industrial and mining enterprises.

III. Fault Improvement for Distribution Boxes

(I) Causes of Faults

1. Faults Caused by the Effect of Ambient Temperature on Low-Voltage Electrical Apparatus

The low-voltage electrical apparatus in a distribution box consists of fuses, AC contactors, residual current operated protectors, capacitors and metering meters. These apparatus are designed and manufactured in accordance with GB1497 "Basic Standard for Low-Voltage Electrical Apparatus", which specifies their normal operating conditions: the upper limit of ambient air temperature shall not exceed 40°C; the average ambient air temperature over 24 h shall not exceed 35°C; the lower limit of ambient air temperature shall not be below -5°C or -25°C.

Distribution boxes for rural grid renovation operate outdoors. They are not only heated by direct sunlight but also generate heat themselves during operation, so in the hot summer season the temperature inside the box can reach above 60°C, far exceeding the ambient temperature specified for these apparatus, thus causing faults due to overheating of the electrical components inside the distribution box.

2. Faults Caused by Product Quality

During rural grid renovation, because of the large number of distribution boxes required and the short construction period, distribution box manufacturers needed low-voltage apparatus urgently and in large quantities, which led to lax quality requirements and caused some products to fail soon after being put into operation. For example, some models of AC contactors burned out their closing coils shortly after the distribution box was put into operation and could not work.

3. Faults Caused by Improper Selection of Electrical Apparatus in Distribution Boxes

During manufacture, the capacity of AC contactors was not properly selected: AC contactors of the same capacity were installed on different outgoing circuits without considering unbalanced three-phase loads, and some outgoing contactors were not selected one current rating higher than the normally selected model. As a result, AC contactors burned out during operation in the hot summer season.

(II) Improvement Measures

1. For distribution boxes with a distribution transformer capacity of 100 kV·A or above, temperature control relays (JU-3 or JU-4 subminiature temperature relays) and axial-flow fans should be installed near the side wall by the heat dissipation window inside the box, on the left side of the cabinet above the control apparatus board, so that when the temperature inside the box reaches a certain value (e.g., 40°C) the exhaust fan starts automatically to force out heat and cool the box.

2. Use protection circuits to prevent faults in the external circuits supplied by the distribution box. Select a compact intelligent phase-loss protector, such as the DA88CM-II motor phase-loss protection module (a Shanghai product), installed in the distribution box to prevent the motor from burning out due to low-voltage phase-loss operation.

3. Improve the wiring of the low-voltage capacitor bank in the original distribution box: change its installation position from the upper terminals of the AC contactor to between the low-voltage incoming line and the metering meter. This prevents inaccurate metering by the metering device when a phase-loss fault occurs in the capacitor circuit or the capacitor is damaged during operation. In addition, capacitors should be of the BSMJ series to ensure reliable component quality and safe operation.

4. If new pole-mounted distribution platforms are added, 2 mm thick stainless steel sheet may be used for the distribution box enclosure, and the box dimensions should be appropriately scaled up (based on the JP4-100/3W model used in rural grid renovation projects, increasing the original box width by about 100 mm, i.e., from 680 mm to 780 mm; the improved box dimensions are 1300 mm × 780 mm × 500 mm), so as to increase the electrical safety distance between branch outgoing lines and between outgoing lines and the box enclosure. This facilitates operation and maintenance and fuse replacement by rural electricians and also improves heat dissipation.

5. Select energy-saving AC contactors (similar to the CJ20SI type), and make sure the contactor coil voltage is connected to the corresponding terminal of the selected residual current operated protector, with correct load matching. When selecting AC contactors, choose products with insulation class A or above, and ensure the rated current of the main circuit contacts is greater than or equal to the load current of the controlled circuit. The rated voltage of the contactor electromagnetic coil is 380 V or 220 V, and the coil may be used within 80%–105% of the rated voltage.

6. Selection of residual current operated protectors. Products must comply with the GB 6829 "General Requirements for Residual Current Operated Protective Devices" standard and be certified by the China Electrotechnical Products Certification Committee. Protectors similar to the LJM(J) series energy-saving, low-sensitivity, time-delay type may be selected. The installation of the protector must comply with the national standard GB 13955-2005 "Installation and Operation of Residual Current Operated Protective Devices". For the breaking time of the residual current protector, when the leakage current equals the rated leakage current, the operating time shall not exceed 0.2 s.

7. Low-voltage cables are used for the incoming and outgoing lines of distribution boxes, and cable selection shall meet technical requirements. For example, for distribution boxes of 30 kVA and 50 kVA transformers, the incoming line uses VV22-35×4 cable and branch outgoing lines use VLV22-35×4 cable of the same specification; for distribution boxes of 80 kVA and 100 kVA transformers, the incoming lines use VV22-50×4 and VV22-70×4 cables respectively, and branch outgoing lines use VLV22-50×4 and VLV22-70×4 cables respectively. The cables are crimped with copper-aluminum cable lugs and then bolted to the terminals in the distribution box.

8. Selection of fuses (RT and NT types). The rated current of the total overcurrent protection fuse on the low-voltage side of the distribution transformer shall be greater than the rated current of the low-voltage side of the distribution transformer, generally 1.5 times the rated current; the rated current of the fuse element shall be determined according to the permissible overload multiple of the transformer and the fuse characteristics. The rated current of the fuse element of the outgoing circuit overcurrent protection fuse shall not be greater than the rated current of the total overcurrent protection fuse; the fuse element rated current shall be selected according to the normal maximum load current of the circuit and shall avoid normal peak currents. The rated current of fuses for shunt capacitor banks may generally be selected as 1.5–2.5 times the rated current of the capacitor.